Cost & Opex · Efficiency Metrics
PUE / WUE
Power Usage Effectiveness and Water Usage Effectiveness — global and regional baselines,
company-reported figures, cooling-technology tradeoffs, and regulatory targets.
Confidence
A Directly reported figure
B Estimated / Derived
C Regional inference / indirect estimate
D Not found / insufficient data
PUE baselines
PUE by company
WUE by scope
Cooling technology
PUE — global & regional baselines BASELINES
Scope PUE Conf. Industry-wide average (global) 1.52 A Largest facilities (global) 1.45 A Best-in-class (top 23% of respondents) <1.3 A EU average (JRC estimate) ~1.6 A EU enterprise data centers ~2.1 B Regulatory target (2030) <1.4 B
PUE — company-reported COMPANY DATA
Company Type PUE Conf. Google Hyperscaler ~1.09 B Meta Hyperscaler ~1.09 B AWS Hyperscaler ~1.15 B Equinix Colocation ~1.39 B Digital Realty Colocation ~1.58 B
WUE — by scope BY SCOPE
Scope WUE (L/kWh) Conf. Industry average (global) 1.8–1.9 B Ideal (air-cooled, no evaporative) 0.0 A Microsoft Arizona facilities 1.52 A Microsoft Singapore facilities 0.02 A Amazon (company-wide average) 0.19 A EU CNDCP commitment (water-stressed sites) ≤0.4 A
Cooling technology — WUE vs. PUE tradeoff TRADEOFF
Cooling technology WUE (L/kWh) PUE Conf. Liquid (direct-to-chip) Near 0 1.05–1.2 B Evaporative 1.5–3.0 15–30% improvement vs. mechanical-only B Best-in-class (NREL reference facility) 0.7 1.06 B
Azraq Derived | Sources: Uptime Institute, European Commission JRC, mgrid.org, and others | Aug 20, 2026